At Rohr Eckhardt Private Limited, we specialize in the design and manufacturing of custom-built Low Voltage (LT) Panels ranging from 1000A to 6300A, engineered to meet the most demanding industrial and utility applications. With a commitment to quality and innovation, our LT Panels offer unmatched safety, flexibility, and performance under varying environmental and load conditions.

Key Features of Low Voltage Panels

✔️ Fully compartmentalized design for enhanced safety and operational clarity

✔️ Easy to install, operate, and maintain — ideal for quick commissioning

✔️ Cost-effective & space-saving architecture

✔️ High degree of safety and operational reliability

✔️ Tailored configurations to meet client-specific requirements

✔️ Aesthetic and compact design suited for modern infrastructure

✔️ Designed to comply with temperature rise limits and stringent quality standards

1000A-6300A Panels
IEC 61439-1/2, IS 8623
ACB and IP rated

🔒 Safety-Focused Design

• Completely enclosed busbar chambers to prevent accidental contact
• Shrouded links in feeder compartments for maximum operator protection
• Dust and vermin-proof construction ensures longevity in all environments
• Busbar systems built to withstand high fault levels

⚙️ Robust Applications

• Industrial complexes
• Power generation & distribution setups
• Commercial buildings
• Utility substations
• Renewable energy installations
• Infrastructure projects

🛠️ Built to Last

• High ambient temperature & humidity tolerance
• Rugged indoor and outdoor applications
• Fixed or draw-out type up to 6300 Amps
• Single or double front access options
• Resistance to short circuits and thermal stress


💡 Why Choose Röhr Eckhärdt LT Panels?

With a legacy rooted in precision and reliability, Rohr Eckhardt Private Limited delivers LT Panels that blend cutting-edge engineering with global quality benchmarks. Designed for low energy consumption and long-term performance, our panels offer you cost-efficiency without compromising on safety or functionality.

1000A - Click to expand ↓
CategorySpecification
Electrical415V AC, 3P+N+E, 50Hz
Rated Current1000A
Short Circuit50kA/1sec
Busbar2×50×10mm (Copper, tin-plated)
Main Breaker1000A ACB (Micrologic trip)
Feeder BreakersMCCBs (250-800A)
MeteringDigital energy meter, ammeter, voltmeter
EnclosureCRCA 2mm, IP42
CoolingNatural ventilation
Cable EntryBottom/top, gland plate
Surge Protection40kA SPD
InterlockingMechanical
TestingIEC 61439 compliant
2000A - Click to expand ↓
CategorySpecification
Electrical415V AC, 3P+N+E, 50Hz
Rated Current2000A
Short Circuit50kA/1sec
Busbar2×100×10mm (Copper, tin-plated)
Main Breaker2000A ACB (Micrologic trip)
Feeder BreakersMCCBs (250-1600A)
MeteringDigital energy meter, ammeter, voltmeter
EnclosureCRCA 2mm, IP42
CoolingNatural ventilation
Cable EntryBottom/top, gland plate
Surge Protection40kA SPD
InterlockingMechanical
TestingIEC 61439 compliant
4000A - Click to expand ↓
CategorySpecification
Electrical415V AC, 3P+N+E, 50Hz
Rated Current4000A
Short Circuit65kA/1sec
Busbar4×100×10mm (Copper, tin-plated)
Main Breaker4000A ACB (Micrologic trip)
Feeder BreakersMCCBs (250-1600A)
MeteringDigital energy meter, ammeter, voltmeter
EnclosureCRCA 2.5mm, IP42/IP55
CoolingForced fans (optional)
Cable EntryBottom/top, gland plate
Surge Protection40kA SPD
InterlockingMechanical/Electrical
TestingIEC 61439 compliant
5000A Click to expand ↓
CategorySpecification
Electrical415V AC, 3P+N+E, 50Hz
Rated Current5000A
Short Circuit65kA/1sec
Busbar4×125×10mm (Copper, tin-plated)
Main Breaker5000A ACB (Micrologic trip)
Feeder BreakersMCCBs (250-1600A)
MeteringDigital energy meter, ammeter, voltmeter
EnclosureCRCA 2.5mm, IP42/IP55
CoolingForced fans (optional)
Cable EntryBottom/top, gland plate
Surge Protection40kA SPD
InterlockingMechanical/Electrical
TestingIEC 61439 compliant
6000A Click to expand ↓
CategorySpecification
Electrical415V AC, 3P+N+E, 50Hz
Rated Current6000A
Short Circuit65kA/1sec
Busbar4×150×10mm (Copper, tin-plated)
Main Breaker6000A ACB (Micrologic trip)
Feeder BreakersMCCBs (250-1600A)
MeteringDigital energy meter, ammeter, voltmeter
EnclosureCRCA 3mm, IP55
CoolingForced fans (mandatory)
Cable EntryBottom/top, gland plate
Surge Protection65kA SPD
InterlockingElectrical (auto-transfer)
TestingIEC 61439 compliant
6300A Click to expand ↓
CategorySpecification
Electrical415V AC, 3P+N+E, 50Hz
Rated Current6300A
Short Circuit65kA/1sec
Busbar4×150×12mm (Copper, tin-plated)
Main Breaker6300A ACB (Micrologic trip)
Feeder BreakersMCCBs (250-1600A)
MeteringDigital energy meter, ammeter, voltmeter
EnclosureCRCA 3mm, IP55
CoolingForced fans (mandatory)
Cable EntryBottom/top, gland plate
Surge Protection65kA SPD
InterlockingElectrical (auto-transfer)
TestingIEC 61439 compliant
Key Differences Summary
Feature Details
Busbar Size 2×50×10mm (1000A) → 4×150×12mm (6300A)
Cooling Natural (≤4000A) → Forced Fans (4000A+ optional, 6000A+ mandatory)
Protection 40kA SPD (≤5000A) → 65kA SPD (≥6000A)
Mechanical → Electrical interlocking (6000A+)
Enclosure Thickness 2mm (1000A) → 3mm (6000A+)
Typical Applications
Current Rating Applications
1000A – 2000A Small factories, commercial complexes
4000A – 5000A Medium industries, hospitals
6000A – 6300A Heavy industries, power substations

LT Panel Detailed Specifications

1000A to 6300A Panels (Siemens/SEIPAN)

1000A LT Panel (Siemens/SEIPAN)

Parameter Specification Additional Details
Busbar System 2×50×10mm Cu, tin-plated Calculation: 1000A ÷ 1.2A/mm² = 833mm² → 2×50×10=1000mm² (20% margin)
Main Breaker (Siemens) 3WL1 1000A ACB with Micrologic 5.0X trip unit Selection Criteria: 1000A continuous, 50kA Icu, 4-pole
Cable Entry Bottom entry with 16×32mm gland plate Option: Top entry available (specify in order)
Interlocking Mechanical interlock between incomer & bus coupler Siemens Part: 3TK2824-0CB4 mechanical interlock kit
Surge Protection Siemens 5SD7 511-6 (40kA, 3P+N) Installation: Directly mounted on busbar
CT/PT 1000/5A CT (Class 0.5 for metering, 5P10 for protection) SEIPAN Model: SCT-1000/5

2000A LT Panel (Siemens/SEIPAN)

Parameter Specification Additional Details
Busbar System 2×100×10mm Cu, tin-plated Calculation: 2000A ÷ 1.2A/mm² = 1666mm² → 2×100×10=2000mm² (20% margin)
Main Breaker (Siemens) 3WL1 2000A ACB with Micrologic 6.0X trip unit Selection Criteria: 2000A continuous, 65kA Icu, 4-pole
Cable Entry Dual-side entry with 20×40mm gland plate SEIPAN Option: Customizable entry positions
Interlocking Mechanical interlock + key exchange system Siemens Part: 3TK2844-0CB4 with key interlock
Surge Protection Siemens 5SD7 611-6 (40kA, 3P+N) with remote alarm contact Coordination: Type 1+2 combined SPD
CT/PT 2000/5A CT (Class 0.2 for energy metering) SEIPAN Model: SCT-2000/5 with DIN96mm mounting

4000A LT Panel (Siemens/SEIPAN)

Parameter Specification Additional Details
Busbar System 4×100×10mm Cu, tin-plated Calculation: 4000A ÷ 1.2A/mm² = 3333mm² → 4×100×10=4000mm² (20% margin)
Main Breaker (Siemens) 3WL2 4000A ACB with Micrologic 7.0X trip unit Selection Criteria: 4000A continuous, 100kA Icu, 4-pole with ground fault protection
Cable Entry Top+bottom entry with 25×50mm gland plate SEIPAN Feature: Anti-dust brush seals for IP55 compliance
Interlocking Electrical interlock (Siemens SIRIUS 3SU1 relays) Logic: Incomer-Coupler interlock via PLC control
Surge Protection SEIPAN SPD-4000 (40kA, 3P+N) with thermal disconnect Installation: Dedicated SPD compartment near incomer
Cooling System 2×120mm axial fans (Siemens 3UF7 310-0AA) Control: Auto ON at 50°C, OFF at 40°C

5000A LT Panel (Siemens/SEIPAN)

Parameter Specification Additional Details
Busbar System 4×125×10mm Cu, tin-plated Calculation: 5000A ÷ 1.2A/mm² = 4166mm² → 4×125×10=5000mm² (20% margin)
Main Breaker (Siemens) 3WL2 5000A ACB with Micrologic 7.0X trip unit Selection Criteria: 5000A continuous, 100kA Icu, 4-pole with advanced metering
Cable Entry Front+rear entry with cable cradle support SEIPAN Option: Fireproof sealing compound for critical applications
Interlocking PLC-based interlock (Siemens S7-1200) with HMI display Function: Auto-transfer logic with priority selection
Surge Protection Siemens 5SD7 711-6 (65kA, 3P+N) with MODBUS monitoring Coordination: 2-stage SPD (Type 1 + Type 2)
Busbar Joints Silver-plated bolted joints with torque markings (45Nm) SEIPAN Standard: Infrared thermography tested during FAT

6000A LT Panel (Siemens/SEIPAN)

Parameter Specification Additional Details
Busbar System 4×150×10mm Cu, tin-plated Calculation: 6000A ÷ 1.1A/mm² = 5454mm² → 4×150×10=6000mm² (10% margin)
Main Breaker (Siemens) 3WL3 6000A ACB with Micrologic 7.0X trip unit Selection Criteria: 6000A continuous, 150kA Icu, 4-pole with arc flash detection
Cable Entry Bottom entry with 30×60mm gland plate + cable bend radius guides SEIPAN Feature: Integrated cable support brackets for 800mm² cables
Interlocking Redundant PLC interlock (Siemens S7-1500) with SCADA integration Logic: Dual-redundant interlock circuits
Surge Protection SEIPAN SPD-6000 (80kA, 3P+N) with RS485 communication Monitoring: Real-time SPD status via MODBUS RTU
Forced Cooling 4×150mm centrifugal fans (Siemens 3UF7 410-0AA) with dust filters Control: VFD-driven speed control based on temperature

6300A LT Panel (Siemens/SEIPAN)

Parameter Specification Additional Details
Busbar System 4×150×12mm Cu, tin-plated Calculation: 6300A ÷ 1.0A/mm² = 6300mm² → 4×150×12=7200mm² (14% margin)
Main Breaker (Siemens) 3WL3 6300A ACB with Micrologic 7.0X trip unit Selection Criteria: 6300A continuous, 150kA Icu, 4-pole with IEC 62606 compliance
Cable Entry Customizable entry ports with 35×70mm gland plates SEIPAN Option: Liquid-tight cable entry systems for outdoor installations
Interlocking SIL-3 certified interlock (Siemens Fail-Safe PLC) Safety: Meets IEC 62061 safety requirements
Surge Protection Siemens 5SD7 811-6 (100kA, 3P+N) with cloud connectivity Integration: Siemens MindSphere compatible
Special Tests Partial discharge test (<10pC) + thermographic scan during FAT SEIPAN Protocol: Witness testing available for customer

1. Busbar Calculation Formula

Formula Current Density
Busbar Size (mm²) = Rated Current (A) / Current Density (A/mm²) 1.2 A/mm² (≤4000A)
1.1 A/mm² (5000A–6000A)
1.0 A/mm² (6300A)

2. Breaker Selection Criteria

Criteria Details
Continuous Current ≥ Panel Rating
Icu ≥ Short-circuit rating (50kA/65kA)
Trip Unit Micrologic X (Siemens)
Configuration 4-pole for complete isolation

3. Cable Entry Best Practices

Practice Specification
Minimum Bend Radius 12× Cable Diameter
Gland Plate Material Stainless Steel (SEIPAN), Aluminum (Siemens)
Sealing Fireproof sealing for critical areas

4. Interlocking Types

Type Mechanical Electrical PLC-Based
Cost Low Medium High
Flexibility Limited Moderate High (programmable)
Vendor Part Siemens 3TK28 series Siemens 3SU1 relays Siemens S7-1200/1500 PLC

Vendor-Specific Recommendations

Vendor Recommendations
Siemens Preferred for 6000A+ panels (3WL3 series with advanced protection)
Seamless integration with TIA Portal for PLC interlocks
SEIPAN Cost-effective for ≤4000A panels
Customizable busbar layouts and cable entry options

Typical Bill of Materials (6300A Example)

Component Siemens Model SEIPAN Equivalent
Main ACB 3WL3 6300A SEI-ACB6300
Surge Protector 5SD7 811-6 SPD-6300-CLOUD
CTs 5A7 1860-6AA SCT-6300/5-HD
Cooling Fans 3UF7 410-0AA SEI-FAN150-4P